| Plan Review Notes For Permit 16110717 |
| Permit Number |
16110717 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-01 10:38:26 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] THE SCOPE OF WORK IS UNCLEAR PLEASE PROVIDE A | | | DETAILED SCOPE OF WORK, FBC 107 | | | | | | 2] SHOW SMOKE ALARM LOACTIONS ON THE FLOOR PLANS PER | | | FBC-R 314 & 315. | | | | | | 3] NEW RECEPTACLES SHALL BE TAMPER RESISTANT & MODIFIED | | | OR NEW CIRCUITS SHALL BE ARC FAULT PROTECTED. FBC-R | | | SECTIONS E3902.13 & E4002.14. | | | | | | 4] IF THE KITCHEN IS BEING REMODELED SHOW GFCI | | | RECPTACLE OUTLETS FOR COUNTER TOP SPACING REQUIREMENTS. | | | FBC-R SECTION E3901.2.4. | | | | | | 5] THE BATHROOM GFI CIRCUIT SHALL BE A MINIMUM 20 AMP | | | BRANCH CIRCUIT. FBC-R SECTION E3703.4. |
|