Plan Review Notes
Plan Review Notes For Permit 16110717
Permit Number 16110717
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-16 08:49:08 
  
 05/30/17 TALKED TO BLANCY MARINO. HE SAID THE PROPOSED
 USE OF THIS PROPERTY IS GOING TO BE FOR COMMERCIAL USE.
 IMPACT FEES ASSESSMENT IS REQUIRED. ALSO, WILL NEED
 FIRE REVIEW. JG.
  
  
 RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROPOSED USE OF THESE BUILDINGS IS NOT CLEAR.
 PROPOSED SITE PLAN SHOWS TWO EXISTING BUILDINGS WITH
 PARKING FOR 5 CARS, INCLUDING PARKING FOR A HANDICAPPED
 PERSON. THIS PARKING LAYOUT IS TYPICAL FOR COMMERCIAL
 USE. FLOOR PLANS SUBMITTED SHOW A LAYOUT FOR A SINGLE
 FAMILY RESIDENCE. CLEARLY IDENTIFY THE PROPOSED USED OF
 EACH BUILDING. NOTE: THE EXISTING USE IS A SINGLE
 FAMILY RESIDENCE WITH A DETACHED GARAGE. IDENTIFY THE
 USE OF EACH BUILDING FOR PROPER PLAN REVIEW. SEC. 102.2
 CITY AMENDMENTS.
  
 2- ACCORDING TO THE WEBSITE STREET VIEW OF THIS HOUSE,
 THE GARAGE DOOR WAS CLOSED. CHANGE OF USE FROM GARAGE
 TO LIVABLE SPACE REQUIRES PLANS REVIEW AND IMPACT FEES
 ASSESSMENT. SEPARATE PERMIT APPLICATION IS REQUIRED FOR
 EACH STRUCTURE. PROVIDE COMPLETE FLOOR PLAN FOR THE
 GARAGE SHOWING PROPOSED USE. SEC. 102.2 CITY
 AMENDMENTS.
  
 3- ACCORDING TO THE WEBSITE STREET VIEW OF THIS HOUSE,
 THE WINDOWS AND DOORS LOOK NEW OR FAIRLY NEW. THERE ARE
 NO CITY RECORDS FOR PERMITS TO REPLACE THE WINDOWS.
 THIS SCOPE OF WORK NEEDS TO BE INCLUDED IN THE PLANS
 AND PERMIT APPLICATION SUBMITTED. SPECIFY THE TYPE AND
 SIZE OF ORIGINAL WINDOWS AND TYPE AND SIZE OF PROPOSED
 WINDOWS. NOTE: SHEET 5 OF 7 SPECIFIES THAT 24SH ARE
 BEDROOM EGRESS WINDOWS. TYPICALLY 24SH SINGLE HUNG
 WINDOWS DON'T COMPLY WITH THE HEIGHT EGRESS
 REQUIREMENTS. PROVIDE MANUFACTURER'S SPECS SHOWING THE
 CLEAR OPENING DIMENSIONS OF THE 24SH WINDOWS TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS. SEC. 704
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 C) FIXED WINDOW AS SHOWN ON PLANS.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 IDENTIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES.
  
 E) SHUTTERS, IF DOOR AND WINDOWS DON'T HAVE IMPACT
 GLAZING. AND PROVIDE COMPLETE INSTALLATION SCHEDULE.
 SEE CITY SAMPLE.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 6- WINDOW TYPE SPECIFIED ON THE FLOOR PLAN ON THE NORTH
 SIDE OF THE DEN ROOM DOESN'T MATCH TYPE OF WINDOW SHOWN
 ON THE NORTH ELEVATION. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL THE SCOPE OF WORK SHOWN ON PLANS.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. REVISE
 VALUATION FOR THE CONSTRUCTION AND FOR THE DESIGN
 PROFESSIONAL FEES.
 NOTE: INCLUDE WINDOW REPLACEMENT. SEE ITEM #3 ABOVE.
  
 8- SHEET 2 OF 7:
 A) CLEARLY SPECIFY THE OCCUPANCY USE/TYPE SPECIFIED ON
 THE WIND INFORMATION ON THE UPPER RIGHT SIDE OF SHEET 2
 OF 7. CLEARLY DEFINE WHAT TYPE OF "RESIDENTIAL
 DWELLING" IS THE PROPOSED USE OF THIS BUILDING. IS THIS
 R3 RESIDENTIAL?. SEE SEC. 310 FBC-BUILDING, 5TH EDITION
 (2014).
  
 B) SPECIFY THE INTERNAL PRESSURE COEFFICIENT ON THE
 WIND INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 NOTE:
 DRIVEWAYS AND APPROACHES REQUIRE SEPARATE PERMITS.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS..
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]