| Plan Review Notes For Permit 16110673 |
| Permit Number |
16110673 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-30 11:17:46 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | 1] PLEASE CLARIFY THE SCOPE OF THE WORK? THE PERMIT | | | APPLICATION CALLS OUT A SERVICE CHANGE AND THE PLANS | | | PROVIDED ARE GENERIC. PROVIDE A SITE SPECIFIC RISER | | | DIAGRAM WITH WIRE & CONDUIT SIZES, COMPLETE LOAD | | | CALCULATION, & GROUNDING DETAIL. FBC 107, NEC 215.5 | | | | | | 2] SHOW OVERCURRENT PROTECTION WITHIN SIGHT OR | | | INTERGRATED AT THE GENERATOR PER NEC 445 & 702. |
|