Plan Review Notes
Plan Review Notes For Permit 16110665
Permit Number 16110665
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-12-14 08:20:26PLANS WERE PASSED BY SUE ELLEN CALDERON GD
2016-11-22 12:21:53PERMIT #16110665
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
  
 1) REVIEW AND CONFIRM THE REQUIREMENTS FOR REQUIRED
 SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS AND IF
 THEY ARE TO BE CONNECTED TO THE INSTALLED FIRE ALARM
 SYSTEM.
 2) ENGINEERED FIRE ALARM AND/OR FIRE SPRINKLER DRAWINGS
 HAVE NOT BEEN SUBMITTED FOR THE MASTER PERMIT
 #16100614. PLEASE NOTE THAT THOSE DRAWINGS MUST BE
 SUBMITTED AS PART OF THE MASTER PERMIT PRIOR TO
 ANY INSPECTIONS ON THE FIRE ALARM SYSTEM. THE
 ENGINEERED DRAWINGS AND THE DRAWINGS FOR THIS PERMIT
 SHALL MATCH; FAILURE TO DO SO WILL RESULT IN A FAILED
 INSPECTION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326