2016-11-22 13:08:09PERMIT #16110660
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
  
 1) REVIEW AND CONFIRM THE REQUIREMENTS FOR REQUIRED
 SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS AND IF
 THEY ARE TO BE CONNECTED TO THE INSTALLED FIRE ALARM
 SYSTEM.
 2) ENGINEERED FIRE ALARM AND/OR FIRE SPRINKLER DRAWINGS
 HAVE NOT BEEN SUBMITTED FOR THE MASTER PERMIT #16100611
 PLEASE NOTE THAT THOSE DRAWINGS MUST BE SUBMITTED AS
 PART OF THE MASTER PERMIT PRIOR TO
 ANY INSPECTIONS ON THE FIRE ALARM SYSTEM. THE
 ENGINEERED DRAWINGS AND THE DRAWINGS FOR THIS PERMIT
 SHALL MATCH; FAILURE TO DO SO WILL RESULT IN A FAILED
 INSPECTION.
 3) SHEET FA3 HAS A DEVICE OMMITTED. PLEASE SEE RED PEN
 MARKS FOR DETAILS.
  