| Plan Review Notes For Permit 16110654 |
| Permit Number |
16110654 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-28 07:35:47 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110654 | | | 12/28/16 | | | | | | 1) SHEETS M-2.1 & M-3.1: EF-1 IN THE WOMEN'S TOILET | | | ROOM HAS A CAPACITY OF 150 CFMS BUT THE EXHAUST RATE | | | REQUIRED PER THE PLAN IS 200 CFMS. PLEASE NOTE THAT PER | | | TABLE 403.3, 210 CFMS IS REQUIRED FOR INTERMITTENT | | | OPERATION. | | | | | | 2) M-2.1 & M-3.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE | | | EXHAUST FAN SERVING THE REMODELED MEN'S TOILET ROOM- | | | MINIMUM 700 CFMS REQUIRED FOR INTERMITTENT OPERATION, | | | AND 500 CFMS FOR CONTINUOUS- TABLE 403.3. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|