| Plan Review Notes For Permit 16110654 |
| Permit Number |
16110654 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-03 08:16:19 | 1) A AT LEAST ONE LAVATORY OUTSIDE THE ACCESSIBLE | | | TOILET COMPARTMENT SHALL COMPLY WITH FAC SEC.213.3.4. | | | 2) AN AMBULATORY ACCESSIBLE STALL IS REQUIRED IN THE | | | MEN'S TOILET ROOM PER THE FAC SEC.604.8.2, 604.8.2.2. | | | 3) DRINKING FOUNTAINS ARE REQUIRED IN THIS SPACE PER | | | 2014 FBC - PLUMBING TABLE 403.1 FOOTNOTE (E) AND FAC | | | SEC.211.2. | | | 4) IDENTIFY THE HANDICAPPED URINAL ON THE PLANS. THE | | | URINAL SHALL COMPLY WITH FAC SEC. 605. | | | 5) THE VENDING MACHINES SHALL COMPLY WITH FAC | | | SEC.228.1. | | | 6) THE ICE MACHINE SHALL BE EQUIPPED WITH A BACKFLOW | | | PREVENTER ON THE WATER LINE PER FPC SEC.608.3. | | | 7) TEMPERED WATER IS REQUIRED FOR THE LAVATORIES IN THE | | | TOILET ROOMS. FPC SEC.607.1. | | | 8) HOT WATER IS REQUIRED AT THE BREAKROOM SINK. FPC | | | SEC. 607.1. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|