| Notes |
| Date |
Text |
| 2016-11-22 15:27:24 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16110654 | | | 11/22/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) SHOW THE LOCATION OF EF-1 ON THE PLAN AND INDICATE | | | CONTROL OPERATION. | | | | | | 3) REFER TOTABLE 6-4 ASHRAE 62.1-2010. KITCHENETTES | | | REQUIRE EXHAUST VENTILATION AT A RATE OF 0.30 CFMS/SF. | | | PLEASE REVISE THE PLAN TO SHOW COMPLIANCE. | | | | | | 4) DIFFUSER SIZES AND SUPPLY CFMS NOT NOTED FOR TWO | | | DROPS IN THE TECH. TOILETS ROOM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|