| 2016-11-16 13:48:53 | 1401 NORTHPOINT PARKWAY |
| | PERMIT #16110654 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PLANS INDICATE THIS IS A BUSINESS OCCUPANCY; |
| | HOWEVER, THIS APPEARS TO BE MIXED USE BUSINESS AND |
| | ASSEMBLY OCCUPANCY. PROVIDE A LIFE SAFETY PLAN BASED |
| | UPON AN ASSEMBLY OCCUPANCY. CURRENTLY TWO EXIT DOORS |
| | ARE SHOWN; HOWEVER, THEY ARE NOT SEPARATED BY A GREAT |
| | ENOUGH DISTANCE TO BE CONSIDERED TWO EXITS. |
| | |
| | DOORS SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS |
| | SHALL SWING IN THE DIRECTION OF EGRESS. |
| | |
| | FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN |
| | OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| | THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| | PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | COULD NOT LOCATE ANY EMERGENCY LIGHTING IN THE ASSEMBLY |
| | AREA. EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A |
| | MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL |
| | LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE |
| | ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT |
| | LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, |
| | NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF |
| | EGRESS AT FLOOR LEVEL. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |