2016-11-16 13:48:531401 NORTHPOINT PARKWAY
 PERMIT #16110654
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THIS IS A BUSINESS OCCUPANCY;
 HOWEVER, THIS APPEARS TO BE MIXED USE BUSINESS AND
 ASSEMBLY OCCUPANCY. PROVIDE A LIFE SAFETY PLAN BASED
 UPON AN ASSEMBLY OCCUPANCY. CURRENTLY TWO EXIT DOORS
 ARE SHOWN; HOWEVER, THEY ARE NOT SEPARATED BY A GREAT
 ENOUGH DISTANCE TO BE CONSIDERED TWO EXITS.
  
 DOORS SERVING AN OCCUPANT LOAD OF 50 OR MORE PERSONS
 SHALL SWING IN THE DIRECTION OF EGRESS.
  
 FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 COULD NOT LOCATE ANY EMERGENCY LIGHTING IN THE ASSEMBLY
 AREA. EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUM OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE