| 2016-11-22 10:57:25 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16110635 | | | 11/21/16 | | | | | | 1) PROVIDE MECHANICAL ALTERATION PLANS. | | | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|