| 2016-11-16 12:33:22 | 5760 CORPORATE WAY | | | PERMIT #16110635 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FOR SEPARATED USE DESIGNS, A BUSINESS OCCUPANCY IS | | | REQUIRED TO BE FIRE SEPARATED FROM A STORAGE OCCUPANCY | | | WITH A 2-HOUR FIRE RATED BARRIER PER FLORIDA FIRE | | | PREVENTION CODE - TABLE 6.1.14.4.1(B) OF NFPA 101. THE | | | DRAWINGS CURRENTLY SHOW NEW AND EXISTING 1-HOUR FIRE | | | RATED SEPARATIONS. FOR NON-SEPARATED USE (NO FIRE RATED | | | SEPARATIONS), THE BUILDING WOULD NEED TO BE PROTECTED | | | THROUGHOUT BY AN AUTOMATIC FIRE SPRINKLER SYSTEM. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|