| 2017-04-28 15:15:26 | 2ND REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN |
| | COMPLIED WITH. |
| | |
| | 2ND REQUEST 2) SHT. F-2 - THE HOSE BIBB SHALL BE |
| | EQUIPPED WITH A SHUTOFF VALVE AND A VACUUM BREAKER. |
| | 2014 FBC SEC.606.2, 608.15.4. |
| | 2ND REQUEST 3) INDICATE ON THE PLANS WHERE THE FLOOR |
| | DRAIN IN THE PUMP ROOM DISCHARGES. THE FLOOR DRAIN |
| | SHALL DISCHARGE TO THE SANITARY AND BE EQUIPPED WITH A |
| | TRAP PRIMER.2014 FBC SEC.1002.4. SUBMNIT SANITARY RISER |
| | DIAGRAM AND ALSO A WATER RISER DIAGRAM FOR ANY AND ALL |
| | DOMESTIC WATER PIPING AND SANITARY DRAIN PIPING FOR |
| | THIS PROJECT. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 2ND REQUEST 5) SUBMIT MANUF. SPECIFICATION SHEETS FOR |
| | THE AQUASTAR CHANNEL DRAIN. WPB AMEND. TO 2014 FBC SEC. |
| | 107.2.1. |
| | 2ND REQUEST 6) THE AUTO FILL SHALL BE EQUIPPED WITH AN |
| | APPROVED BACKFLOW PREVENTION DEVICE. 2014 FBC- |
| | PLUMBING, SEC. 608.13, 608.15. |
| | 2ND REQUEST 7) SHT. F-4 - PLACE A NOTE / DETAILS ON THE |
| | PLANS AS TO HOW THE PIPE SUPPORTS WILL BE SECURED TO |
| | THE SUBSTRATE AND THE SPACING OF SAID SUPPORTS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |
| | |