| 2017-02-14 08:01:23 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PLEASE CLARIFY IF THERE ARE LUMINAIRES TO BE PLACED | | | IN FOUNTAIN, IF SO PROVIDE DATA SHEETS FOR ALL LIGHTING | | | AND ASSOCIATED EQUIPMENT PER NEC 680- PART5 FOUNTAINS. | | | 2. SHOW GFCI PROTECTION FOR 20AMP PUMP PER NEC 680.21C | | | 3. PROVIDE BONDING SCHEME FOR THE FOUNTAIN AND | | | ASSOCIATED METALS TO BE BONDED PER NEC 680.53 | | | 4. ADDRESS ZONING COMMENTS. | | | 5. PROVIDE A NOTE ON PLANS TO INDICATE NEC 300.5 | | | REQUIREMENTS FOR ALL UNDERGROUND RACEWAYS. | | | 6. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4- | | | COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3- | | | VOLTAGE DROP | | | 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC | | | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE | | | VERBIAGE IN CODE. | | | 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | PROFESSIONAL | | | | | | | | | |
|