2017-02-14 08:01:23INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE CLARIFY IF THERE ARE LUMINAIRES TO BE PLACED
 IN FOUNTAIN, IF SO PROVIDE DATA SHEETS FOR ALL LIGHTING
 AND ASSOCIATED EQUIPMENT PER NEC 680- PART5 FOUNTAINS.
 2. SHOW GFCI PROTECTION FOR 20AMP PUMP PER NEC 680.21C
 3. PROVIDE BONDING SCHEME FOR THE FOUNTAIN AND
 ASSOCIATED METALS TO BE BONDED PER NEC 680.53
 4. ADDRESS ZONING COMMENTS.
 5. PROVIDE A NOTE ON PLANS TO INDICATE NEC 300.5
 REQUIREMENTS FOR ALL UNDERGROUND RACEWAYS.
 6. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3-
 VOLTAGE DROP
 7. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  