Plan Review Notes
Plan Review Notes For Permit 16110574
Permit Number 16110574
Review Stop P
Sequence Number 1
Notes
Date Text
2016-12-20 16:16:391ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. PER FBC ACC 604.9.6
  
 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE!!TOP
 OF THE GRIPPING SURFACE!!, PER FBC ACC 609.4
  
 3. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 606
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4. TEMPERED WATER REQUIRED AT LAVATOR PERFBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 5. PLEASE PROVIDE A SITE PLAN SHOWING THE SAN SEWER,
 WATER AND STORM PIPING METERS AND BACK FLOW PER WPB
 AMEND TO FBC 107.2.1
  
 6. SEPARATE PERMIT REQUIRED FOR BACK FLOW. PER WPB
 UTILITIES