| Plan Review Notes For Permit 16110574 |
| Permit Number |
16110574 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-02 17:08:45 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110574 | | | 12/2/16 | | | | | | 1) PROVIDE A VENTILATION CALCULATION FOR THE NEW GUARD | | | HOUSE IN COMPLIANCE WITH TABLE 403.3, AND SHOW HOW | | | OUTDOOR AIR WILL BE PROVIDED TO THE SPACE- SEESECTION | | | 401.2. | | | | | | 2) THE AC SCHEDULE DOES NOT SHOW ANY DATA FOR HEATING. | | | IS THIS UNIT A HEAT PUMP? PLEASE REFER TO SECTION 309.1 | | | AND SHOW COMPLIANCE. | | | | | | 3) THE ENGINEER OF RECORD MUST PROVIDE HIS SIGNATURE | | | AND SEAL TO THE SUMMARY AC CALCULATIONS- SECTION | | | C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|