| 2016-12-12 08:23:18 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA CUT SHEET SUBMITTALS FOR GENERATOR, |
| | ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO |
| | FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, |
| | SIGNAGE, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. |
| | 2. PLEASE ADD A GENERAL NOTE TO SHEET TO INDICATE THE |
| | REQUIREMENTS OF NEC 300.5D3 AND TABLE 300.5 FOR MINIMUM |
| | COVER REQUIREMENTS FOR CONDUITS AND THE PLACEMENT OF A |
| | WARNING RIBBON FOR THE SERVICE LATERAL CONDUCTORS SHOWN |
| | FOR THIS PROJECT. A NOTE WILL SUFFICE |
| | 3. ADD A NOTE TO MAINTAIN ALL ELECTRICAL EQUIPMENT |
| | ABOVE THE BASELINE FLOOD ELEVATION PER STATE AND CITY |
| | REGULATORY AGENCIES. |
| | 4. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR |
| | FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7 |
| | 5. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| | INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC |
| | 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE |
| | VERBIAGE IN CODE. |
| | 6. PROVIDE AIC CALCULATION FOR THE NEW SERVICE SHOWN. |
| | FBC 107.3.5 |
| | 7. LABEL GFCI PROTECTED ALL EXTERIOR RECEPTACLES. NEC |
| | 210.8B(4) |
| | 8. LABEL INTERIOR RECEPTACLES WITHIN 6FT OF THE SINKS |
| | TO BE GFCI PROTECTED. NEC 210.8B(5) |
| | 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |