| Notes |
| Date |
Text |
| 2021-03-25 15:20:28 | GOLF COURSE REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) NEW COMMENTS - DRAWINGS DESIGNED BY AN ENGINEER OR | | | ARCHITECT NEED TO BE SIGNED AND SEALED BY THE ENGINEER | | | OR ARCHITECT - FBC 107.1 | | | | | | PREVIOUS COMMENTS WERE NOT ADDRESSED - (PLEASE SHOW THE | | | CODE IN EFFECT FOR THE DESIGN) | | | | | | 1. REVISE PLAN TO STATE WHETHER ADA OR FAIR HOUSING OR | | | BOTH APPLY. IT APPEARS THAT BOTH APPLY (SERVES | | | CONDOMINIUM OWNERS AND THEIR GUESTS; ALSO A PLACE OF | | | PUBLIC ACCOMODATION SERVING THE PUBLIC AND HOTEL). | | | | | | 2. IF ADA IS APPLICABLE, REVISE PLAN TO STATE GOVERNING | | | CODE; REVISE PLAN TO SHOW COMPLIANCE WITH FBC A 1006. | | | | | | YOU MAY FIND THIS DOCUMENT USEFUL: | | | | | | HTTPS://WWW.ACCESS-BOARD.GOV/ATTACHMENTS/ARTICLE/592/GO | | | LF.PDF | | | | | | 3. IF FAIR HOUSING IS APPLICABLE, REVISE PLAN TO STATE | | | GOVERNING CODE; REVISE PLAN TO SHOW COMPLIANCE WITH FBC | | | A FAIR HOUSING GUIDELINES. | | | | | | | | | | | | |
|