2017-05-08 15:15:411- NEW FLAT ROOF NOA 16-0413.06 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.1
 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
 B) IF SELECTED ASSEMBLY DOESN'T MET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS WILL BE
 REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. APPROVED ASSEMBLIES THAT ARE LIMITED BY
 GENERAL LIMITATION #9 MAY NOT BE USED IF THE DESIGN
 PRESSURES ARE TOO LOW. LIMITATION #9 DOESN'T ALLOW RAS
 117 CALCULATIONS.
 RESPONSE: REPEAT COMMENT. RESPONSE LETTER STATE THAT
 "INFORMATION HAS BEEN UPDATED ON RAS 17 CALCULATION".
 SIGNED AND SEALED RAS 117 CALCULATIONS WERE NOT
 SUBMITTED.
  