| 2017-05-08 13:15:13 | RESIDENTIAL (R3) ADDITION/ALTERATION, THIRD MECHANICAL |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- REVISE EQUIPMENT LOAD CALCULATIONS SUBMITTED: |
| | A) FRONT DOOR ORIENTATION DOESN'T MATCH ACTUAL FRONT |
| | DOOR ORIENTATION. HOUSE IS NOT FACING THE NORTH WEST. |
| | SEE SURVEY OR PALM BEACH COUNTY PROPERTY APPRAISER AND |
| | REVISE AS REQUIRED. CALCULATIONS NEED TO BE DONE BASED |
| | ON THE ACTUAL DIRECTIONAL ORIENTATION OF THE BUILDING |
| | AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. SAME LOAD CALCULATIONS WERE |
| | RE-SUBMITTED. |
| | |
| | B) GLAZING AND WALLS INFORMATION SUBMITTED DON'T MATCH |
| | INFORMATION SHOWN ON THE ENERGY CALCULATIONS. REVISE AS |
| | REQUIRED TO MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. SAME LOAD CALCULATIONS WERE |
| | RE-SUBMITTED. |
| | |
| | C) CLARIFY WHY THERE IS NO PEOPLE CONSIDERED FOR THE |
| | CALCULATIONS. THE PROPOSED UNIT IS DEDICATED FOR THIS |
| | PLAYROOM ZONE ONLY. CLARIFY WHY THERE IS NO PEOPLE |
| | CONSIDERED IN THE CALCULATIONS. SEC. R103.2 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | RESPONSE: REPEAT COMMENT. SAME LOAD CALCULATIONS WERE |
| | RE-SUBMITTED. |
| | |
| | |
| | NOTES: |
| | ****A) PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***B) PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | ONE. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS FOR |
| | REFERENCE. |
| | |
| | |