| 2017-02-03 17:50:41 | 1- FLAT ROOF NOA 14-0827.14 SUBMITTED: | | | A) IT CAN NOT BE USED BECAUSE THIS NOA IS FOR | | | "CEMENTITIOUS WOOD FIBER DECKS". THIS IS NOT THE TYPE | | | OF DECK SPECIFIED ON PLANS. NEED TO PROVIDE PRODUCT | | | APPROVAL FOR WOOD DECKS AS SPECIFIED ON PLANS. FAC | | | 61G20-3.002(33). | | | | | | B) CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES REQUIRED BY SEC. R301.1 | | | FBC-RESIDENTIAL. | | | RESPONSE: REPEAT COMMENT. | | | | | | C) IF SELECTED ASSEMBLY DOESN'T MET THE DESIGN | | | PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL, THEN | | | SIGNED AND SEALED RAS 117 CALCULATIONS WILL BE | | | REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. APPROVED ASSEMBLIES THAT ARE LIMITED BY | | | GENERAL LIMITATION #9 MAY NOT BE USED IF THE DESIGN | | | PRESSURES ARE TOO LOW. LIMITATION #9 DOESN'T ALLOW RAS | | | 117 CALCULATIONS. | | | RESPONSE: REPEAT COMMENT. |
|