2017-02-03 11:26:09RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE EQUIPMENT LOAD CALCULATIONS SUBMITTED:
 A) FRONT DOOR ORIENTATION DOESN'T MATCH ACTUAL FRONT
 DOOR ORIENTATION. HOUSE IS NOT FACING THE NORTH WEST.
 SEE SURVEY OR PALM BEACH COUNTY PROPERTY APPRAISER AND
 REVISE AS REQUIRED. CALCULATIONS NEED TO BE DONE BASED
 ON THE ACTUAL DIRECTIONAL ORIENTATION OF THE BUILDING
 AS REQUIRED BY SEC. R403.6.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 B) GLAZING AND WALLS INFORMATION SUBMITTED DON'T MATCH
 INFORMATION SHOWN ON THE ENERGY CALCULATIONS. REVISE AS
 REQUIRED TO MATCH. SEC. R103.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 C) CLARIFY WHY THERE IS NO PEOPLE CONSIDERED FOR THE
 CALCULATIONS. THE PROPOSED UNIT IS DEDICATED FOR THIS
 PLAYROOM ZONE ONLY. CLARIFY WHY THERE IS NO PEOPLE
 CONSIDERED IN THE CALCULATIONS. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTES:
 ****A) PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***B) PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 ONE. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  
  