Plan Review Notes
Plan Review Notes For Permit 16110559
Permit Number 16110559
Review Stop R
Sequence Number 1
Notes
Date Text
2016-12-13 16:36:471- FLAT ROOF NOA 12-0716.18 SUBMITTED:
 CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FORM NOA
 12-0716.18 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.1 FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY
 DOESN'T MET THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.1 FBC-RESIDENTIAL, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED. SEE GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA SUBMITTED. APPROVED ASSEMBLIES
 THAT ARE LIMITED BY GENERAL LIMITATION #9 MAY NOT BE
 USED IF THE DESIGN PRESSURES ARE TOO LOW. LIMITATION #9
 DOESN'T ALLOW RAS 117 CALCULATIONS.
  