Plan Review Notes
Plan Review Notes For Permit 16110559
Permit Number 16110559
Review Stop E
Sequence Number 1
Notes
Date Text
2016-11-21 12:29:19JOB PERMIT NUMBER: 16110559
 JOB ADDRESS: 4101 SHELLY RD
 WEST PALM BEACH FLORIDA
 DATE: NOVEMBER 21, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] PROVIDE AN ELECTRICAL RISER DIAGRAM INCLUDE WIRE &
 CONDUIT SIZES, SHOW GROUNDING & BONDING DETAIL. FBC 107
  
 2] SHOW A DISCONNECT SNAP-SWITCH FOR THE INTERIOR AHU
 WITHIN SIGHT AND IN A READY ACCESSIBLE LOCATION PER NEC
 440.14.
  
 3] SHOW ALL SMOKE ALARM LOCATIONS ON THE FLOOR PLAN IN
 ACCORDANCE WITH FBC-R 314.3.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  