Plan Review Notes
Plan Review Notes For Permit 16110559
Permit Number 16110559
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-12 17:49:15RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
 NOTE: THIS MAY BE DONE LATER WHEN THE PLANS ARE
 APPROVED AND BEFORE PRINTING THE PERMIT.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE ENERGY CALCULATIONS WITH PLANS AND
 PRODUCT APPROVALS SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 3- NORTH ARROW ORIENTATION SHOWN ON ALL PLANS IS
 INCORRECT. REVISE AS REQUIRED. SEE PALM BEACH COUNTY
 PROPERTY APPRAISER OR SURVEY. SEC. 107.2.1 CITY
 AMENDMENTS. THIS IS IMPORTANT FOR CORRECT ENERGY
 CALCULATIONS AND EQUIPMENT LOAD CALCULATIONS.
  
 4- SHEET S.1:
 A) PLANS ARE REFERENCING THE 2010 FBC. THE CURRENT CODE
 IS THE FBC-5TH EDITION (2014). REVISE THE DESIGN
 CRITERIA, AND ALL THE STRUCTURAL NOTES THAT REFERENCE
 THE 2010 CODE AS REQUIRED BY CHAPTER 553 F.S.
  
 B) STRUCTURAL NOTES: REVISE THE ROOF LIVE LOAD OF
 10PSF. SEE SEC. R301.6 FBC-RESIDENTIAL AND REVISE AS
 REQUIRED.
  
 C) THIS IS NOT ALTERATION LEVEL LL. THIS IS AN
 ADDITION. REVISE THE DESIGN CRITERIA NOTE #7 AS
 REQUIRED. SEC. 507 FBC-EXISTING BUILDING, 5TH EDITION
 (2014).
  
 5- TYPICAL EXTERIOR WALL DETAIL ON SHEET S.2: R-30
 INSTALLED IN 2 X 10 ROOF JOIST DON'T ALLOW ROOF CROSS
 VENTILATION AS REQUIRED BY SEC. R806.3 FBC-RESIDENTIAL,
 5TH EDITION (2014). CROSS VENTILATION REQUIRES A LEAST
 1 INCH SPACE BETWEEN THE INSULATION AND THE BOTTOM OF
 THE ROOF SHEATHING. R-30 INSULATION IS ABOUT 9-1/2"
 THICK, THEREFORE THE 1 INCH SPACE IS NOT PROVIDED.
 RE3VISE AS REQUIRED.
  
 6- FLAT ROOF NOA 12-0716.18 SUBMITTED:
 CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FORM NOA
 12-0716.18 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.1 FBC-RESIDENTIAL. NOTE: IF SELECTED ASSEMBLY
 DOESN'T MET THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.1 FBC-RESIDENTIAL, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED. SEE GENERAL LIMITATION
 #7 ON LAST PAGE OF NOA SUBMITTED. APPROVED ASSEMBLIES
 THAT ARE LIMITED BY GENERAL LIMITATION #9 MAY NOT BE
 USED IF THE DESIGN PRESSURES ARE TOO LOW. LIMITATION #9
 DOESN'T ALLOW RAS 117 CALCULATIONS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR;
 A) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL11120-R8 SUBMITTED IS FOR 2010 FBC VERSION. NEED
 CURRENT 2014 FBC VERSION. CHAPTER 553 F.S.
  
 B) WINDOW MULLIONS AS SPECIFIED ON PLANS. AND, CLEARLY
 SPECIFY MULLION SIZE TO VERIFY DESIGN PRESSURES. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 C) SLIDING DOORS. FLORIDA PRODUCT APPROVAL FL11109-R4
 SUBMITTED IS FOR 2010 FBC VERSION. NEED CURRENT 2014
 FBC VERSION. CHAPTER 553 F.S.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE SPECIFIC CONNECTOR OR DESIGNER OF
 RECORD TO LIST FLORIDA PRODUCT APPROVAL NUMBER NEXT TO
 EACH SPECIFIED CONNECTOR.
  
 E) PRE-CAST LINTELS AS SPECIFIED ON PLANS.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- SPECIFY CARBON MONOXIDE ALARM WITHIN 10'-0" OF EACH
 BEDROOM AS REQUIRED BY SEC. R315 FBC-RESIDENTIAL.
  
 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT (EVEN FOR
 OWNER/BUILDER) AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS
 UPDATED TO $35,000. THE PERMIT FEE BALANCE IS $901.98.
  
 NOTE:
 PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT
 TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712