Plan Review Notes
Plan Review Notes For Permit 16110554
Permit Number 16110554
Review Stop M
Sequence Number 1
Notes
Date Text
2016-11-29 15:08:371ST REVIEW FBC-2014 MECHANICAL, EXISTNG BUILDING CODES
 PERMIT #16110554
 11/29/16
  
 1) SHEET 2: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHEET 2: INDICATE THE DUCT, DIFFUSER, AND GRILL
 SIZES IN THE CONF RM, AND OFFICES 4 AND 5. SHOW THE
 SUPPLY AND RETURN CFMS AT EACH DIFFUSER AND GRILL.
  
 3) SHEET 2: PROVIDE AN AIR DEVICE SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER