| Plan Review Notes For Permit 16110554 |
| Permit Number |
16110554 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-29 15:08:37 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTNG BUILDING CODES | | | PERMIT #16110554 | | | 11/29/16 | | | | | | 1) SHEET 2: REFER TO SECTION 809.2 FBC-14 EXISTING | | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 | | | FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES | | | THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) SHEET 2: INDICATE THE DUCT, DIFFUSER, AND GRILL | | | SIZES IN THE CONF RM, AND OFFICES 4 AND 5. SHOW THE | | | SUPPLY AND RETURN CFMS AT EACH DIFFUSER AND GRILL. | | | | | | 3) SHEET 2: PROVIDE AN AIR DEVICE SCHEDULE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|