  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] PROVIDE A PANEL SCHEDULE WITH MATCHING DESIGNATED
 CIRCUITS ON THE FLOOR PLAN. FBC-107
  
 2] EMERGENCY/EXIT LIGHTING SHALL BE FED BY LIGHTING
 CIRCUIT OF SAME LOCAL AREA. NEC 700.12(F)(4)
  
 3] SHOW A FIRE PENETRATION DETAIL IN COMPLIANCE WITH
 FBC 714 & NEC 300.21.
  
 4] FIRE ALARM SHALL BE SUBMITTED UNDER A SEPARATE
 PERMIT. A NOTE WILL SUFFICE.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  