| 2016-11-16 17:57:51 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | 1] SUBMITTAL DOCUMENTS CONSISTING OF CONSTRUCTION | | | DOCUMENTS, STATEMENT OF SPECIAL INSPECTIONS, | | | GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED | | | IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION. FBC | | | 107 | | | | | | 2] PROVIDE FPL AVAILABLE FAULT CURRENT LETTER & SHOW | | | AIC CALCULATIONS TO VERIRY SHORT CIRCUIT RATING OF | | | ELECTRICAL EQUIPMENT. NEC 110.24, 110.10, 110.9 | | | | | | 3] OUTSIDE TRANSFORMER SECONDARY CONDUCTORS MUST | | | TERMINATE TO A SINLGE CIRCUIT BREAKER OR SINGLE SET OF | | | FUSES THAT LIMIT THE LOAD TO THE AMPACITY OF THE | | | CONDUCTORS PER NEC 240.21(C)(4). OTHERWISE SHOW | | | COMPLIANCE WITH 25' LIMIT & PRIMARY TO SECONDARY RATIO | | | REQUIREMENTS FOUND IN NEC 240.21(B)(3). | | | |
|