Plan Review Notes
Plan Review Notes For Permit 16110519
Permit Number 16110519
Review Stop E
Sequence Number 1
Notes
Date Text
2016-11-16 17:57:511ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
 1] SUBMITTAL DOCUMENTS CONSISTING OF CONSTRUCTION
 DOCUMENTS, STATEMENT OF SPECIAL INSPECTIONS,
 GEOTECHNICAL REPORT AND OTHER DATA SHALL BE SUBMITTED
 IN TWO OR MORE SETS WITH EACH PERMIT APPLICATION. FBC
 107
  
 2] PROVIDE FPL AVAILABLE FAULT CURRENT LETTER & SHOW
 AIC CALCULATIONS TO VERIRY SHORT CIRCUIT RATING OF
 ELECTRICAL EQUIPMENT. NEC 110.24, 110.10, 110.9
  
 3] OUTSIDE TRANSFORMER SECONDARY CONDUCTORS MUST
 TERMINATE TO A SINLGE CIRCUIT BREAKER OR SINGLE SET OF
 FUSES THAT LIMIT THE LOAD TO THE AMPACITY OF THE
 CONDUCTORS PER NEC 240.21(C)(4). OTHERWISE SHOW
 COMPLIANCE WITH 25' LIMIT & PRIMARY TO SECONDARY RATIO
 REQUIREMENTS FOUND IN NEC 240.21(B)(3).
  