2016-11-21 10:46:02JOB PERMIT NUMBER: 16110470
 JOB ADDRESS: 5500 VILLAGE BLVD
 WEST PALM BEACH FLORIDA
 DATE: NOVEMBER 21, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] PROVIDE A MOUNTING DETAIL FOR THE CEILING GRID LIGHT
 FIXTURES IN ACCORDANCE WITH NEC 410.36(B). SHOW
 SUPPORTING DETAIL IN COMPLIANCE WITH ACOUSTICAL SYSTEM
 PROVISIONS ASTM 635C & 636C.
  
 2] PLEASE ADD EXIT SIGNS IN THE COPY MAIL AREA FOR THE
 DOOR LEADING TO THE EGRESS STAIRS & ADD AN EXIT SIGN
 FOR THE EXIT DISCHARGE WITHIN THE BREAKROOM. FBC-1011
  
 3] AT LEAST 50 % OF ALL 125 V 15 & 20 AMP RECEPTACLES
 INSTALLED IN PRIVATE OR OPEN OFFICES INCLUDING MODULAR
 PARTITIONS SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL
 DEVICE PER FBC-E SECTION C405.7.1 CONFORMANCE WITH
 ASHREA 90.1, 8.4.2. THIS APPLIES TO THE POWER POLE
 FEEDS FOR THE MODULAR OFFICES.
  
 4] GFCI PROTECTION IS REQUIRED WHERE RECEPTACLES ARE
 INSTALLED WITHIN 6' OF THE SINK & INSIDE BATHROOMS. NEC
 210.8(B) PLEASE VERIFY BREAKROOM & RESTROOM.
  
 5] ACCESS CONTROL & FIRE ALARM PLANS SHALL BE SUBMITTED
 UNDER A SEPARATE PERMIT. A NOTE WILL SUFFICE.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER