| 2016-11-21 10:46:02 | JOB PERMIT NUMBER: 16110470 |
| | JOB ADDRESS: 5500 VILLAGE BLVD |
| | WEST PALM BEACH FLORIDA |
| | DATE: NOVEMBER 21, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] PROVIDE A MOUNTING DETAIL FOR THE CEILING GRID LIGHT |
| | FIXTURES IN ACCORDANCE WITH NEC 410.36(B). SHOW |
| | SUPPORTING DETAIL IN COMPLIANCE WITH ACOUSTICAL SYSTEM |
| | PROVISIONS ASTM 635C & 636C. |
| | |
| | 2] PLEASE ADD EXIT SIGNS IN THE COPY MAIL AREA FOR THE |
| | DOOR LEADING TO THE EGRESS STAIRS & ADD AN EXIT SIGN |
| | FOR THE EXIT DISCHARGE WITHIN THE BREAKROOM. FBC-1011 |
| | |
| | 3] AT LEAST 50 % OF ALL 125 V 15 & 20 AMP RECEPTACLES |
| | INSTALLED IN PRIVATE OR OPEN OFFICES INCLUDING MODULAR |
| | PARTITIONS SHALL BE CONTROLLED BY AN AUTOMATIC CONTROL |
| | DEVICE PER FBC-E SECTION C405.7.1 CONFORMANCE WITH |
| | ASHREA 90.1, 8.4.2. THIS APPLIES TO THE POWER POLE |
| | FEEDS FOR THE MODULAR OFFICES. |
| | |
| | 4] GFCI PROTECTION IS REQUIRED WHERE RECEPTACLES ARE |
| | INSTALLED WITHIN 6' OF THE SINK & INSIDE BATHROOMS. NEC |
| | 210.8(B) PLEASE VERIFY BREAKROOM & RESTROOM. |
| | |
| | 5] ACCESS CONTROL & FIRE ALARM PLANS SHALL BE SUBMITTED |
| | UNDER A SEPARATE PERMIT. A NOTE WILL SUFFICE. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |