| 2017-01-26 09:29:21 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16110448 |
| | ADD: 7130 OKEECHOBEE BLVD. |
| | CONT: LAGASSE' POOL |
| | TEL: 954-587-1000 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: THURS. JAN. 26/ 2017 |
| | ACTION: DENIED |
| | |
| | IMPORTANT NOTICE!!!!!!!WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & |
| | REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1) 2ND REQUEST. SHEET 1 OF 7 SHOW SECTIONS OF FENCING |
| | BY OTHERS BETWEEN BUILDINGS. THIS PLAN DEPICTS THE |
| | OUTLINE OF THE APARTMENT BUILDINGS AND RECREATION/ |
| | LEASING CENTER WHICH SURROUND THE POOL AND POOL DECK. |
| | THE BUILDING ELEVATION PLANS OF THESE BUILDINGS DOES |
| | NOT INDICATE HOW SEPARATION FROM THE APARTMENT PATIO |
| | DECKS (FIRST FLOOR) AND THE POOL AND POOL DECK AREAS |
| | AND COMPLIANCE WITH 2014 FBC-B 454.1.3.1.9. ACCESS |
| | THROUGH THE BARRIER OR FENCE FROM DWELLING UNITS, SUCH |
| | AS HOMES, APARTMENTS, MOTEL ROOMS AND HOTEL ROOMS, |
| | SHALL BE THROUGH SELF-CLOSING, SELF-LATCHING LOCKABLE |
| | GATES OF 48 INCH (1219 MM) MINIMAL HEIGHT FROM THE |
| | FLOOR OR GROUND WITH THE LATCH LOCATED A MINIMUM OF 54 |
| | INCHES (1372 MM) FROM THE BOTTOM OF THE GATE OR AT |
| | LEAST 3 INCHES (76 MM) BELOW THE TOP OF THE GATE ON THE |
| | POOL SIDE. |
| | |
| | 2) 2ND REQUEST. SHEET 1 OF 7 THE SAME POOL SEPARATION |
| | ISSUE OCCURS WITHIN THE RECREATION/ LEASING BUILDING |
| | AND POOL/ POOL DECK AREA PLEASE SHOW COMPLIANCE WITH: |
| | 2014 FBC-B 454.1.3.1.9. ACCESS THROUGH THE BARRIER OR |
| | FENCE FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS, |
| | MOTEL ROOMS AND HOTEL ROOMS, SHALL BE THROUGH |
| | SELF-CLOSING, SELF-LATCHING LOCKABLE GATES OF 48 INCH |
| | (1219 MM) MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH |
| | THE LATCH LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM |
| | THE BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM) |
| | BELOW THE TOP OF THE GATE ON THE POOL SIDE. IF THE |
| | SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING |
| | AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR |
| | INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF |
| | SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864 |
| | MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED |
| | FLOOR OR GROUND. DOORED ACCESS POINTS FROM PUBLIC ROOMS |
| | SUCH AS LOBBIES OR CLUB HOUSES NEED NOT BE THROUGH |
| | GATES IF THE DOOR(S) MEET THE SAME SELF-CLOSING, |
| | SELF-LATCHING REQUIREMENTS AS A GATE. GATES SHALL OPEN |
| | OUTWARD AWAY FROM THE POOL AREA. |
| | |
| | 3) COMPLIED. POOL HEATERS/ 2014 ENERGY CODE C404.7.3 |
| | COVERS |
| | |
| | 4)COMPLIED. POOL FOR RESIDENCE USE ONLY, UNDER FAIR |
| | HOUSING REQUIREMENTS. |
| | |
| | 5) NEW COMMENT: SHEETS CH P-1, CH-P2 & CHE-4. THE PLANS |
| | ARE COPIED, REDUCED AND WITH A PRINTED DIGITAL |
| | SIGNATURE. FLORIDA ADMINISTRATIVE CODE 61G15-23.005 |
| | (3)(C) A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE |
| | USED ON ELECTRONICALLY SIGNED AND SEALED ENGINEERING |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | IF THESE SHEETS ARE FOR REFERENCE USE ONLY, MARK AS |
| | SUCH. REFERENCE USE ONLY!!! |
| | |
| | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |