| 2016-11-26 07:23:38 | 1) SHT. 2 OF 7 - THE DRAIN FROM THE VAK-PAK IS NOT |
| | PERMITTED TO DISCHARGE TO THE STORM DRAINAGE SYSTEM PER |
| | CITY CODE OF ORDINANCES CHAPT.90, ART. V, SEC. 90-203 |
| | (A). |
| | 2) SUBMIT MANUF. SPECCIFICATIONS FOR THE HEAT PUMPS. |
| | HEAT PUMPS SHALL COMPLY WITH THE 2014 FBC-ENERGY, |
| | SEC.C404.7.1 AND TABLE C404.2 FOR THE REQUIRED MINIMUM |
| | EFFICIENCIES. |
| | 3) TIME SWITCHES OR OTHER CONTROL METHODS THAT CAN |
| | AUTOMATICALLY TURN OFF AND ON HEATERS TO A PRESET |
| | SCHEDULE SHALL BE INSTALLED ON ALL HEATERS AND HEAT |
| | PUMPS. FBC-ENERGY SEC.C404.7.2. |
| | 4)PLEASE CLARIFY WHY THE CLUBHOUSE PLANS HAVE BEEN |
| | SUBMITTED. IF THEY ARE FOR REFERENCE ONLY, MARK THE |
| | PLANS AS SUCH. OTERWISE THE PLANS NEED TO BEAR THE |
| | SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL OF |
| | RECORD. FAC RULE 61G15-23.001. |
| | 5) PROVIDE VERIFICATION THAT THE FILTRATION RATE HAS |
| | BEEN DESIGNED TO INCLUDE A FLOW RATE OF 3/4 GPM FOR |
| | EACH NON - TRANSIENT LIVING UNIT PER 2014 FBC |
| | SEC.454.1.1.1. |
| | 6) PROVIDE VERIFICATION THAT THE MAXIMUM FILTRATION |
| | RATE IN GALLONS PER MINUTE PER SQUARE FOOT OF FILTER |
| | AREA FOR THE CARTRIDGE FILTERS DOES NOT EXCEED 0.375 |
| | PER 2014 FBC SEC.454.1.6.5.5.1. |
| | 7) SHOW THE DISTANCE OF THE HOSE BIBB AND RIINSE SHOWER |
| | FROM THE POOL. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 8) SHT. 7 OF 7 - NOTES #6, 7, & 8 REFER TO FBC CODE |
| | SECTIONS 802 ( NOTE #6), 424.2.9 (NOTE #7), & FBC |
| | 605.21 (NOTE #8). THESE CCODE SECTIONS HAVE NOTHING TO |
| | DO WITH SWIMMING POOL CONSTRUCTION. CLARIFY. |
| | |