2016-11-26 07:23:381) SHT. 2 OF 7 - THE DRAIN FROM THE VAK-PAK IS NOT
 PERMITTED TO DISCHARGE TO THE STORM DRAINAGE SYSTEM PER
 CITY CODE OF ORDINANCES CHAPT.90, ART. V, SEC. 90-203
 (A).
 2) SUBMIT MANUF. SPECCIFICATIONS FOR THE HEAT PUMPS.
 HEAT PUMPS SHALL COMPLY WITH THE 2014 FBC-ENERGY,
 SEC.C404.7.1 AND TABLE C404.2 FOR THE REQUIRED MINIMUM
 EFFICIENCIES.
 3) TIME SWITCHES OR OTHER CONTROL METHODS THAT CAN
 AUTOMATICALLY TURN OFF AND ON HEATERS TO A PRESET
 SCHEDULE SHALL BE INSTALLED ON ALL HEATERS AND HEAT
 PUMPS. FBC-ENERGY SEC.C404.7.2.
 4)PLEASE CLARIFY WHY THE CLUBHOUSE PLANS HAVE BEEN
 SUBMITTED. IF THEY ARE FOR REFERENCE ONLY, MARK THE
 PLANS AS SUCH. OTERWISE THE PLANS NEED TO BEAR THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL OF
 RECORD. FAC RULE 61G15-23.001.
 5) PROVIDE VERIFICATION THAT THE FILTRATION RATE HAS
 BEEN DESIGNED TO INCLUDE A FLOW RATE OF 3/4 GPM FOR
 EACH NON - TRANSIENT LIVING UNIT PER 2014 FBC
 SEC.454.1.1.1.
 6) PROVIDE VERIFICATION THAT THE MAXIMUM FILTRATION
 RATE IN GALLONS PER MINUTE PER SQUARE FOOT OF FILTER
 AREA FOR THE CARTRIDGE FILTERS DOES NOT EXCEED 0.375
 PER 2014 FBC SEC.454.1.6.5.5.1.
 7) SHOW THE DISTANCE OF THE HOSE BIBB AND RIINSE SHOWER
 FROM THE POOL. WPB AMEND. TO FBC SEC. 107.2.1.
 8) SHT. 7 OF 7 - NOTES #6, 7, & 8 REFER TO FBC CODE
 SECTIONS 802 ( NOTE #6), 424.2.9 (NOTE #7), & FBC
 605.21 (NOTE #8). THESE CCODE SECTIONS HAVE NOTHING TO
 DO WITH SWIMMING POOL CONSTRUCTION. CLARIFY.
  