| Plan Review Notes For Permit 16110372 |
| Permit Number |
16110372 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-16 15:19:00 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE A ELECTRICAL PLAN TO INCLUDE A PANEL | | | SCHEDULE SHOWING WIRE, BREAKER & CONDUIT SIZE, CICUIT | | | DESIGNATION TO MATCH THE FLOOR PLAN. FBC 107 | | | | | | 2] PROVIDE MANUFACTURE SPECIFICATIONS OF NEW EQUIPMENT | | | TO BE INSTALLED | | | | | | 3] GFCI PROTECTION IS REQUIRED FOR VENDING MACHINES, | | | PLUG RECEPTACLES IN COMMERCIAL KITCHENS, & OUTLETS | | | INSTALLED WITHIN 6' OF THE OUTSIDE EDGE OF A SINK. NEC | | | 422.51 & 210.8(B) |
|