| Plan Review Notes For Permit 16110325 |
| Permit Number |
16110325 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-15 12:10:48 | 16110325 | | | 288 FLAMINGO DRIVE | | | SF REMODEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | | | | PROVIDE THE LOCATION OF THE PANEL BOARD. INCLUDE A | | | PANEL SCHEDULE SHOWING THE NEW CIRCUITS WITH | | | APPROPRIATE OVERCURRENT PROTECTION. NEC 230.70, FBC R | | | E3405.1 | | | | | | VERIFY ALL NEW RECEPTACLES ARE TAMPER RESISTANT. NEC | | | 406.2; FBC R E4002.14 | | | | | | VERIFY ALL NEW CIRCUITS ARE AFCI PROTECTED. NEC 210.12; | | | FBC R E3902.12 | | | | | | CEILING ELECTRICAL BOXES IF INTENDED FOR SUPPORT OF | | | PADDLE FANS MUST BE LISTED FOR THAT USE. NEC 422.18; | | | FBC R 3905.9 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. 2014 FBC R314, 315 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6654(OFFICE) | | | 561-373-3701(CELL) | | | | | | |
|