2016-12-12 18:59:54PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET 2, GENERAL NOTE 6 SPECIFIES CITRUS COUNTY
 AMMENDMENTS. THIS SHOULD BE CITY OF WEST PALM BEACH
 AMENDMENTS. FBC 107.2.1
  
 2) ALSO ON SHEET 2, UNDER SOIL, NOTE 1 IS NOT LEGIBLE.
 I BELIEVE IT SHOULD STATE 95 PERCENT DENSITY. FBC
 107.2.1
  
 3) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS
 HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM)
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM)
 MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF
 FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL
 OPEN DIRECTLY TO THE OUTSIDE AIR.
 R806.2 MINIMUM VENT AREA. THE MINIMUM NET FREE
 VENTILATING AREA SHALL BE 1/150 OF THE AREA OF THE
 VENTED SPACE.
  
 4) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR
 R101.5.1.1.2. SUBMIT TWO SETS OF ENERGY COMPLIANCE
 FORMS AS REQUIRED.
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE ASPHALT ROOF SHINGLES, MODIFIED BITUMEN ROOFING
 MATERIAL (WITH ENHANCED FASTENING CALCULATIONS),
 CASEMENT WINDOWS, STRUCTURAL MULLIONS AND THE GABLE
 LOUVER VENT.
  
 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  