| Notes |
| Date |
Text |
| 2016-11-08 14:15:43 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | AS PER DAIKIN SPECIFICATIONS THE RATED CFM OUTPUT AT .1 | | | FRICTION LOST FOR DV24PVCC14 IS 700 CFM. MAXIMUM OUTPUT | | | AT .1 FRICTION LOST IS 770 CFM. AS PER YOUR SUBMITTED | | | PLANS THE FIRST FLOOR TOTAL SUPPLY OUTLET CFM OUTPUT IS | | | 500 CFM. AS PER YOUR SUBMITTED PLANS THE SECOND FLOOR | | | TOTAL SUPPLY OUTLET CFM OUTPUT IS 575 CFM. | | | | | | (1) PROVIDE PROPER SUPPLY AIR OUTLET CFM DISTRIBUTION | | | BALANCE AS PER RATED CFM MANUFACTURER SPECIFICATIONS. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|