| 2016-11-16 14:52:03 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] NEC 600.5 SIGN OUTLET SHALL BE SUPPLIED BY A | | | MINNIMUM DEDICATED 20 AMP BRANCH CIRCUIT, IF AN | | | EXISTING CIRCUIT IS TO BE USED PLEASE ADD A NOTE ON THE | | | PLANS. | | | | | | 2] THE STATED VALUATION OF $1,000 IS TOO LOW FOR THE | | | PROPOSED SIGN. THE PERMIT VALUATION AND PERMIT FEE MUST | | | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED | | | CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION | | | ACCORDINGLY AND PROVIDE AN OWNER SIGNED CONTRACT FOR | | | VERIFICATION. FBC-109 | | | | | | |
|