| 2016-11-29 16:43:42 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16110246 | | | 11/29/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 7-1 ASHRAE 170-2008 AND | | | TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT | | | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR | | | AIR, MINIMUM OUTDOOR AIR CHANGES, MINIMUM TOTAL AIR | | | CHANGES, AND PRESSURE RELATIONSHIPS BETWEEN | | | | | | ADJACENT ROOMS AND AREAS. | | | | | | 2) SHEET M3.0: FIRE DAMPERS ARE REQUIRED FOR THE SUPPLY | | | AND RETURN DUCTS PNETRATING THE FIRE-RATED | | | CORRIDOR/MAINTENANCE SHOP WALL- SEE SECTION 607.5.2 | | | FBC-14 MECHANICAL. | | | | | | 3) M3.0: SHOW ALL BRANCH DUCT AND TRUCK SIZES- MANY ARE | | | NOT INDICATED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|