2016-11-29 16:43:421ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #16110246
 11/29/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 7-1 ASHRAE 170-2008 AND
 TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR, MINIMUM OUTDOOR AIR CHANGES, MINIMUM TOTAL AIR
 CHANGES, AND PRESSURE RELATIONSHIPS BETWEEN
  
 ADJACENT ROOMS AND AREAS.
  
 2) SHEET M3.0: FIRE DAMPERS ARE REQUIRED FOR THE SUPPLY
 AND RETURN DUCTS PNETRATING THE FIRE-RATED
 CORRIDOR/MAINTENANCE SHOP WALL- SEE SECTION 607.5.2
 FBC-14 MECHANICAL.
  
 3) M3.0: SHOW ALL BRANCH DUCT AND TRUCK SIZES- MANY ARE
 NOT INDICATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER