| 2016-11-23 16:18:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET FP 10 - THERE ARE INCORRECT REFERENCES TO THE |
| | CURRENT EDITIONS OF THE FIRE CODES. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | |
| | PLEASE MAKE CORRECTIONS AND ENSURE COMPLIANCE WITH THE |
| | UPDATED CODES. |
| | |
| | |
| | |
| | 2) SHEET A101 & A 40 - DOOR 109-5 IS INDICATED AS BEING |
| | IN A RATED WALL SIMILAR TO DOORS 109-1 & 109-3; |
| | HOWEVER, THE DOOR SCHEDULE DOES SHOW IT WITH THE SAME |
| | 45 MIN RATING. |
| | |
| | PLEASE REVIEW AND CLARIFY OR MAKE CORRECTIONS. |
| | |
| | |
| | |
| | 3) SHEET A51 & E50 - ROOMS INDICATED AS GROUP 1 THRU 4 |
| | ARE NOT SHOWING EXIT SINGS ABOVE THE EXIT DOORS. THESE |
| | ROOMS, THOUGH NOT LABLED AS ASSEMBLY, MAY FUNCTION AS |
| | ASSEMBLY SPACES OR MULTIFUNCTIOAL SPACES THAT MAY |
| | EXPAND THEIR OCCUPANCY LOADS. |
| | |
| | PLEASE CLARIFY THE FUNCTION OF THESE ROOMS AND HOW THE |
| | FUNCTIONAL USE WILL BE CONTROLLED TO THAT WILL NOT |
| | EXCEED THE OCCUPANCY LOAD OR PROVIDE EXIT SIGNS AS EACH |
| | DOOR. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |