Plan Review Notes
Plan Review Notes For Permit 16110246
Permit Number 16110246
Review Stop E
Sequence Number 1
Notes
Date Text
2016-12-01 15:53:011ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PLEASE CLARIFY IF THESE GROUP ROOMS ARE CLASSIFIED
 AS PATIENT EXAMINATION ROOMS FOR PROVISIONS OF NEC 517
 GROUNDING & BONDING.
  
 2] COMPLY WITH EXIT SIGN REQUIREMENTS PER FIRE MARSHALL
 COMMENTS IN GROUP ROOMS 1-4.
  
 3] ELECTRIC DRINKING FOUNTAIN SHALL BE GFCI PROTECTED.
 NEC 422.52
  
 4] LOW VOLTAGE & FIRE ALARM SHALL BE UNDER A SEPERATE
 PERMIT. ADD A BLOCK NOTE.
  
 5] ADDITIONAL COMMENTS MAY BE NOTED UPON RE-SUBMITTAL.