| Plan Review Notes For Permit 16110246 |
| Permit Number |
16110246 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-12-01 15:53:01 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PLEASE CLARIFY IF THESE GROUP ROOMS ARE CLASSIFIED | | | AS PATIENT EXAMINATION ROOMS FOR PROVISIONS OF NEC 517 | | | GROUNDING & BONDING. | | | | | | 2] COMPLY WITH EXIT SIGN REQUIREMENTS PER FIRE MARSHALL | | | COMMENTS IN GROUP ROOMS 1-4. | | | | | | 3] ELECTRIC DRINKING FOUNTAIN SHALL BE GFCI PROTECTED. | | | NEC 422.52 | | | | | | 4] LOW VOLTAGE & FIRE ALARM SHALL BE UNDER A SEPERATE | | | PERMIT. ADD A BLOCK NOTE. | | | | | | 5] ADDITIONAL COMMENTS MAY BE NOTED UPON RE-SUBMITTAL. |
|