Plan Review Notes
Plan Review Notes For Permit 16110246
Permit Number 16110246
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-08 09:06:46BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110246 PAVILION 4 JFK MEDICAL
 CENTER- NORTH CAMPUS
 ADD: 2201 45TH ST.
 CONT: TBD/ ARCH. MIKE SNOWDENL
 TEL: 502-893-1875
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. DEC. 08/2016
 ACTION: DENIED
  
 1) SHEET 06_A41 PARTIAL FIST FLOOR PLAN THE BOTTOM
 RIGHT PORTION OF THE PLAN INDICATES THE BUILDINGS SMOKE
 COMPARTMENTS. THE AREA DESIGNATED AS A THE LARGER FLOOR
 PLAN DOES NOT MATCH THE SMOKE COMPARTMENTATION. THE
 PLAN LEGEND DOES NOT INDICATE IF THE REPRESENTED LINES
 ARE SMOKE COMPARTMENTS OR IF THESE LINES REPRESENT THE
 LIMITATION OF THE WORK AREA? SHEET 005_A31 LIFE SAFETY
 PLAN DOES INDICATE A WALL RATING LEGEND.
  
 1A) THE LOWER RIGHT FLOOR PLAN HAS THE WALL ADJACENT TO
 THE DINING ROOM AND CORRIDOR 107 AS ONE WALL FOR
 COMPARTMENTATION WHEREAS THE FLOOR PLAN SHOWS THE
 OPPOSITE WALL OF CORRIDOR 107. DISCREPANCY IN PLANS,
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) SMOKE COMPARTMENTATION BETWEEN THE NEW GROUP ROOMS
 AND THE BOARD ROOM ON THE LARGER FLOOR PLAN VERSES THE
 LOWER RIGHT SMOKE COMPARTMENT PLAN.107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 1C) PLEASE NOTE DOOR 109-5 APPEARS TO BE IN A 1 HOUR
 FIRE RATED WALL, THE DOOR SCHEDULE DOES NOT INDICATE
 ANY FIRE RATING. SEE 2014 FBC-B TABLE 716.5.
  
 2) SHEET 005_A31 LIFE SAFETY PLAN AND LEGEND SHOWS THE
 4 NEW GROUP ROOMS AS INPATIENT TREATMENT ROOMS WITH
 FLOOR AREA IN SQ. F./ OCCUPANT 240 SQ. FT. PER TABLE
 1004.2.1 FBC-B. WHY NOT USE THE 15 SQ. FT. PER
 OCCUPANT? GROUP ROOMS 3 & 4 WHEN COMBINED WOULD HAVE AN
 OCCUPANT LOAD OF 50 OR MORE THAT WOULD REQUIRE A 2ND
 MEANS OF EGRESS.
  
 3) SHEET 004_A21 THE DEMO PLAN SHOWS IN THE COMMON AREA
 NOTE # 6 INDICATING THE EXISTING STOREFRONT TO BE
 REMOVED AND REPLACED WITH NEW WINDOWS. SHEET 007_A41A
 INDICATES S NEW EXTERIOR WALL SECTION IN GROUP ROOM #
 2. SHEET 003_S20 DETAILS 1 & 2 BOTH SHOW NEW BOX BEAM
 HSS GIRT DETAIL 2 INDICATES WELDED CONNECTIONS.
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS.
 2014 FBC-B 2204.1 WELDING
 201404.4.2 BOLTING.
  
 4A SHOW COMPLIANCE WITH 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 4B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) SHEET 012_A81 DETAIL # 11 SHOWS A WALL CUT SECTION
 THROUGH THE NEW EXTERIOR WALL. THE NOTE # 10 INDICATES
 WIRE LATH , NOTE #9 INDICATES THE USE OF ? INCH
 EXTERIOR GYPSUM SHEATHING. WHAT IS LACKING IN THESE
 NOTES IS COMPLIANCE WITH SECTION :
 2014 FBC-B 2510.5.2.2 USE OF GYPSUM SHEATHING BACKING.
 GYPSUM SHEATHING IS PERMITTED AS A BACKING FOR METAL OR
 WIRE FABRIC LATH AND CEMENT PLASTER ON WALLS. A
 WATER-RESISTIVE BARRIER SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 2510.6.
  
 2014 FBC-B 2510.6 WATER-RESISTIVE BARRIERS.
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION 1404.2 AND, WHERE APPLIED OVER WOOD-BASED
 SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 1405.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
  
 6) PLEASE NOTE THIS BUILDING IS LOCATED IN AN A8 FLOOD
 ZONE(BASE FLOOD ELEVATION 14.0 FT. NGVD. A FLOOD ZONE
 CERTIFICATE WILL BE REQUIRED SHOWING THE ELEVATION OF
 THE FINISH FLOOR, PLEASE PROVIDE THE ELEVATION IN NGVD.
 THE VALUE OF THE BUILDING CAN NOT BE DETERMINED SINCE
 THERE ARE SEVERAL BUILDINGS ON THE SAME LOT. UNTIL
 VALUE OF THE BUILDING IS UNKNOWN THE CITY CAN NOT
 DETERMINE IF
 SUB-STANIAL IMPROVEMENTS HAVE BEEN MET, THE OTHER ISSUE
 THAT WILL NEED TO BE DETERMINED IS THE DATE THIS
 BUILDING WAS BUILT TO SEE IF IT IS A PRE-FIRM OR POST
 FIRM.
  
 FBC BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES / (12 INCHES OF
 ELEVATION IF PLANS WERE SUBMITTED AFTER SEPT. 12/2016)
 .
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS
 A/C PADS OR OTHER SLABS FOR GENERATORS
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  