| Plan Review Notes For Permit 16110230 |
| Permit Number |
16110230 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-14 11:29:14 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110230 | | | 11/14/16 | | | | | | 1) THE 18X18" RETURN GRILL IS UNDERSIZED PER SECTION | | | 601.5- 600 SQ. INCHES REQUIRED. | | | | | | 2) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION: THE MECHANICAL CLOSET SHALL BE CONSIDERED | | | A "PLENUM CHAMBER" AND MUST BE CONSTRUCTED IN | | | ACCORDANCE WITH SECTION 602.1. PLEASE VERIFY | | | COMPLIANCE. | | | | | | 3) THE BMP CLIP SUBMITTAL HAS A COPIED ENGINEER'S | | | SIGNATURE AND SEAL WHICH IS NOT ACCEPTABLE PER SECTION | | | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. PROVIDE SITE | | | SPECIFIC WIND LOAD ENGINEERING DESIGNED BY A FL. | | | LICENSED ENGINEER- SEE SECTION 301.15 FBC-14 | | | MECHANICAL, AND SECTION 1609 FBC-14 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|