| Plan Review Notes For Permit 16110180 |
| Permit Number |
16110180 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2017-03-01 12:28:37 | 6TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16110180 | | | 3/1/17 | | | | | | 1) THE REVISED EXHAUST VENTILATION AND AIR BALANCE | | | CALCULATIONS INDICATE ERV'S ARE REQUIRED FOR AHU'S #1, | | | 3, 4, & 5 BECAUSE THE THE AMOUNT OF O/A REQUIRED IS | | | EXCEEDING 50% OF THE DESIGN SUPPLY FAN AIRFLOW RATE- | | | SEE TABLE C403.2.6 FBC-14 ENERGY CONSERVATION. PLEASE | | | NOTE THAT A PRODUCT DATA SHEET HAS BEEN SUBMITTED FOR A | | | LIGHT COMMERCIAL ERV HOWEVER THE UNIT(S) ARE NOT SHOWN | | | ON THE PLAN. IT ALSO APPEARS THAT THE O/A REQUIRED FOR | | | THE OVERNIGHT DOG AREA AT 1397 CFMS WILL FAR EXCEED THE | | | COOLING CAPACITY OF THE 5-TON AHU-1 SYSTEM. | | | | | | 2) M-2: AC SYSTEMS #1, 4 & 5 ARE NOT FUNCTIONING IN THE | | | RETAIL AREA- PLEASE DESIGNATE THEIR LOCATIONS TO | | | CORRELATE WITH THE PLAN. | | | | | | 3) ADVISORY: TO AVOID ANY FURTHER PLAN REJECTIONS, | | | PLEASE CONSULT WITH A LICENSED MECHANICAL ENGINEER. | | | PLEASE NOTE THAT ALL OCCUPIED SPACES MUST BE PROVIDED | | | WITH EITHER NATURAL OR MECHANICAL VENTILATION (SECTION | | | 401.2), AND ACTIVE OR SPACE HEATING SYSTEMS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|