| 2017-02-17 07:43:49 | 4TH REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16110180 |
| | 2/17/17 |
| | |
| | NO CORRECTIONS TO THE PLANS OR RESPONSES TO THE 3RD |
| | REVIEW COMMENTS HAVE BEEN PROVIDED. I HAVE COPIED THE |
| | COMMENTS BELOW FOR REVIEW- PLEASE COMPLY. |
| | |
| | 1) 3RD REQUEST FOR EXHAUST VENTILATION CALCULATIONS FOR |
| | ALL SYSTEMS- TABLE 403.3 |
| | |
| | 2) 3RD REQUEST TO PROVIDE COMPLETE EXHAUST SYSTEM |
| | DRAWINGS INCLUDING THE INDOOR DOG PLAY ROOMS. THE |
| | DRAWINGS AND DETAILS SHALL INCLUDE THE EXHAUST DUCT |
| | TYPES AND SIZES, DUCT RUNS AND TERMINATION LOCATIONS. |
| | PLEASE NOTE THAT ENGINEERING DETAILS FOR INSTALLATION |
| | OF ANY ROOFTOP FANS OR TERMINATION CAPS WILL BE |
| | REQUIRED. |
| | |
| | 3) 2ND REQUEST FOR THE ARCHITECT OF RECORD TO PROVIDE |
| | SHOP DRAWING APPROVAL OF THE AC CALCULATIONS. |
| | |
| | 4) 2ND REQUEST FOR THE ENERGY COMPLIANCE CHECKLIST TO |
| | BE FILLED OUT. |
| | |
| | 5) 3RD REQUEST FOR COMPLETE AIR BALANCE CALCULATIONS. |
| | PLEASE NOTE THE CALCULATION M-1 DOES NOT INCLUDE THE |
| | O/A AIR SUPPLIED BY AHU-3 AND THE REQUIRED EXHAUST |
| | SYSTEMS IN THE INDOOR DOG AREAS. |
| | |
| | 6) PROVIDE THE DUCT LAYOUT PLAN FOR AHU-3. |
| | |
| | 7) THE CU TIE DOWN DETAIL IS INCOMPLETE. PLEASE PROVIDE |
| | THE GAUGE OF THE STEEL STRAP OR MANUFACTURER'S |
| | SPECIFICATIONS, AND HOW THE CLIP WILL BE FASTENED TO |
| | THE CONDENSER JACKET. |
| | |
| | 8) 2ND REQUEST TO SHOW THE LOCATION OF THE DS DETECTORS |
| | IN THE RETURN AIR SYSTEMS OF THE AHU'S. |
| | |
| | 9) PLEASE CLARFY WHAT TYPE OF AUTOMATIC O/A DAMPERS ARE |
| | PROPOSED FOR AHU'S 1 & 2. ARE THESE MOTORIZED DAMPERS? |
| | IF SO, PLEASE SEE SECTION C402.4.5.2 FBC-14 ENERGY |
| | CONSERVSATION AND PROVIDE MANUFACTURER'S |
| | SPECIFICATIONS. |
| | |
| | 10) REFER TO SECTION 401.4 AND PROVIDE THE REQUIRED |
| | CLEARANCE DISTANCE MEASUREMENTS FOR THE O/A INTAKES TO |
| | EXHAUST OUTLETS OR OTHER CONTAMINANT SOURCES, AND |
| | VEHICULAR DRIVE AREAS SUCH AS DRIVEWAYS AND PARKING |
| | LOTS |
| | |
| | 11) INDICATE HOW THE O/A OPENINGS WILL BE PROTECTED IN |
| | COMPLIANCE WITH SECTION 401.5. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |