| Plan Review Notes For Permit 16110180 |
| Permit Number |
16110180 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-01-28 06:09:50 | 1) THE BREAK ROOM SINK SHALL COMPLY WITH THE 2014 | | | FBC-ACCESS. SECS.212, 606 AND 305. SHOW THE HEIGHT OF | | | THE TOP OF THE COUNTERTOP/SINK FROM THE FINISH FLOOR. | | | 2) THE WALL FINISH IN THE NEW TOILET ROMM SHALL COMPLY | | | WITH 2014 FBC SEC. 1210. SHT.THE FINISH SCHEDULE ON | | | SHT.A-2 SHOWS THE WALLS AS PAINT. CLARIFY. | | | 3) THE SANITARY RISER DOES NOT COMPLY WITH THE | | | FBC-PLUMBING CODE. | | | A) THE WASHING MACHINE SHALL BE INSTALLED ON A MINIMUM | | | 3 INCH STACK. FPC SEC.406.2. | | | B) THE DOG TUBS ARE NOT VENTED. FPC 901.2.1. | | | C) THE DISHWASHER SHALL DRAIN INDIRECTLY PER FPC | | | SEC.802.1.6. | | | D) THE DRINKING FOUNTAIN IS NOT VENTED. FPC 901.2.1. | | | 4) SHT. A-1 ( DEMO PLAN) IS MISSING. IT IS LISTED ON | | | THE COVER PAGE. CLARIFY. | | | 5) HOT WATER IS REQUIRED TO THE WASHING MACHINE. FPC | | | SEC.607.1. | | | 6) THE ENTIRE WATER SYSTEM ( HOT & COLD ) IS SIZED IN | | | 1/2 INCH PIPE. REFER TO FPC SEC.604.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|