2016-12-27 08:49:022ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16110180
 12/27/16
  
 1) THE REQUESTED EXHAUST FAN SCHEDULES AND EXHAUST
 VENTILATION CALCULATIONS WERE NOT PROVIDED.
  
 2) THE REQUESTED EXHAUST DUCT DETAILS- TYPES AND SIZES
 OF DUCTS AND TERMINATION LOCATIONS WERE NOT PROVIDED.
  
 3) THE REQUESTED AC CALCULATIONS MUST BEAR TRHE SHOP
 DRAWING APPROVAL STAMP AND SIGNATURE OF THE DESIGN
 PROFESSIONAL OF RECORD.
  
 4) THE REQUESTED ENERGY COMPLIANCE SUBMITTAL WAS
 SUBMITTED WITHOUT THE PRINTED OR SIGNED NAMES OF THE
 DESIGN PROFESSIONALS OR THE OWNER/AGENT- SEE PAGE 3.
  
 5) THE REQUESTED ENERGY COMPLIANCE SUBMITTAL WAS
 SUBMITTED WITHOUT THE MANDATORY REQUIREMENTS CHECKLIST
 COMPLETED- SEE PAGE 8.
  
 6) THE ENERGY COMPLIANCE SUBMITTAL INCORRECTLY LISTS
 TWO 5-TON AC SYSTEMS AT 16 SEER, HOWEVER ONLY THE NEW
 SYSTEM IS 16 SEER.
  
 7) THE REQUESTED AIR BALANCE CALCULATION WAS NOT
 PROVIDED.
  
 8) THE REQUESTED WIND LOAD ENGINEERING AND STRUCTURAL
 DETAILS FOR THE CU AND CU PAD WERE NOT PROVIDED.
  
 9) THE EQUIPMENT SCHEDULE FOR THE NEW 5-TON AC
 INCORRECTLY LISTS THE WEIGHT AT 9.7 LBS.
  
 10) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF THE NEW AND EXISTING 5-TON AC SYSTEMS,
 UNLESS MANUFACTURER'S SPECIFICATIONS INDICATE THE UNITS
 ARE INCAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY
 AIR- SECTION 606.2.1.
  
 11) PROVIDE AN AIR DEVICE SCHEDULE.
  
 12) NEW DRYER: REFER TO SECTION 504 AND PROVIDE A)
 MANFACTURER'S SPECIFICATIONS FOR THE DRYER. B) EXHAUST
 DUCT DETAILS INCLUDING THE DUCT RUN AND DUCT
 TERMINATION. C) MAKEUP AIR DETAILS- SEE SECTION 504.5.
  