| 2016-11-14 08:51:35 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, |
| | ENERGY CONSERVATION CODES |
| | PERMIT #16110180 |
| | 11/14/16 |
| | |
| | THE MECHANICAL PLANS DESIGNED BY SANDRA PUERTA |
| | ARCHITECT ARE DEFICIENT AND NOT IN COMPLIANCE WITH |
| | CURRENT CODES AND STANDARDS. |
| | |
| | 1) PROVIDE EQUIPMENT SCHEDULES ON THE PLAN FOR THE NEW |
| | AND EXISTING AC SYSTEMS, AND THE VARIOUS EXHAUST FANS |
| | SHOWN IN THE DRAWINGS. |
| | |
| | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY |
| | CONSERVATION. |
| | |
| | 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR, AND THE REQUIRED AND |
| | PROVIDED CFM'S OF EXHAUST AIR. |
| | |
| | 4) PROVIDE AN AIR BALANCE CALCULATION. |
| | |
| | 5) THE PROJECT IS DEFINED AS A CHANGE OF OCCUPANCY PER |
| | SECTION 202 FBC-14 EXISTING BUILDING CODE. REFER TO |
| | SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND SUBMIT |
| | DOCUMENTATION OF COMPLIANCE. SEE SECTION 401.2 FOR |
| | COMPLIANCE PATH OPTIONS. |
| | |
| | 6) PROVIDE AN AIR DEVICE SCHEDULE ON THE PLAN,. |
| | |
| | 7) INDICATE THE SIZES OF THE SUPPLY AND RETURN DUCTS, |
| | DIFFUSERS, DISTRIBUTION BOXES, AND RETURN GRILLS SHOWN |
| | ON THE LAYOUT DRAWING, AND SHOW CFM AMOUNTS AT EACH |
| | SUPPLY DIFFUSER AND RETURN GRILL. |
| | |
| | 8) PROVIDE A COMPLETE DUCT LAYOUT FOR AHU-2 & AHU-3 |
| | |
| | 9) INDICATE HOW OUTSIDE AIR IS BEING SUPPLIED TO THE |
| | ROOMS AND SPACES, AND REFER TO SECTION C403.2.4.4 FOR |
| | SHUTOFF DAMPER REQUIREMENTS. |
| | |
| | 10) REFER TO TABLE 403.3 FOOTNOTE B: AIR FROM THE DOG |
| | GROOMING ROOM IS NOT PERMITTED TO RECIRCULATE INTO THE |
| | ADJACENT RETAIL AREA. |
| | |
| | 11) REFER TO TABLE 403.3 FOOTNOTE B: HOW IS AIR BEING |
| | RETURNED TO AHU-3? NO RETURN DUCTS OR GRILLS ARE SHOWN. |
| | PLEASE NOTE THAT AHU-1 MUST BE A COMPLETELY SEALED UNIT |
| | WITH A DUCTED RETURN BECAUSE IT SHARES THE SAME |
| | MECHANICAL CLOSET WITH AHU-2. THE AIR FROM THESE TWO |
| | SYSTEMS CANNOT COMMUNICATE. |
| | |
| | 12) PROVIDE EXHAUST VENTILATION DETAILS: SHOW THE TYPES |
| | AND SIZES OF EXHAUST DUCTS, THE DUCT RUNS, AND THE |
| | TERMINATION LOCATIONS- SEE SECTION 501.2- 501.3.1.1. |
| | |
| | 13) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | THE ACCU #3- SECTION 301.15. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |