| Date |
Text |
| 2016-11-12 16:21:01 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | 1. PLEASE PROVIDE AN ACCURATE ONE-LINE RISER THAT |
| | EXISTING AS CONDUCTORS SIZE AT 1/0 IS UNDERSIZED FOR A |
| | 200A MAIN. FBC 107.3.5 |
| | 2. DELETE RESIDENTIAL CODE NOTES FROM THE ELECTRICAL |
| | NOTES, ONLY PROVIDE WHAT IS APPLICABLE FOR THIS |
| | PROJECT. FBC 107.3.5 |
| | 3. CLARIFY HEX NOTES TO FLOOR PLAN. NOT SHOWN. |
| | 4. SHOW A COMPLETE PANEL BOARD SCHEDULE NOT JUST |
| | ADDITIONAL AS SHOWN. THERE ARE NEW POWER AND LIGHTING |
| | OUTLETS SHOWN. NEW EXHAUST FANS, NEW A/H AND A/C MUST |
| | BE ACCOUNTED FOR. |
| | 5. SHOW CIRCUIT DESIGNATION FOR ALL NEW LIGHTING AND |
| | POWER OUTLETS AND EQUIPMENT. SHOW WHAT PANEL THEY |
| | ORIGINATE FROM TO VERIFY LOAD CALCULATION DO NOT |
| | EXCEEDED AMPS PER SIZE OF MAINS. |
| | 6. SHOW DESIGN COMPLIANCE PER FBC ENERGY CONSERVATION |
| | CODE. A GENERAL NOTE WILL NOT SUFFICE, SHOW SYMBOLS OF |
| | AUTOMATIC CONTROL LIGHTING AND LIGHTING DENSITIES FOR |
| | AREAS. |
| | 7. NEW A/C EQUIPMENT MUST PROVIDE A W/P GFCI RECEPTACLE |
| | WITHIN 25FT OF UNIT FOR SERVICE. NEC 210.63. SHOW A |
| | DISCONNECT FOR A/C UNIT AND A/H UNIT INSIDE. |
| | 8. LABEL ON FLOOR PLAN WHAT IS NEW OR EXISTING FOR A |
| | COMPLETE REVIEW. |
| | 9. EM LIGHTING TO BE PROVIDED TO NEW BATHROOM AREA. |
| | 10. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM |
| | TO INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD |
| | MARKINGS; SEE VERBIAGE IN CODE. |
| | 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |