| Plan Review Notes For Permit 16110161 |
| Permit Number |
16110161 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-01-09 19:11:24 | RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW | | | CHECKLIST. | | | CODE: FBC, 5TH EDITION (2014). | | | | | | 1- THE LOAD CALCULATIONS ARE CONSIDERING 7 PEOPLE AS | | | THE OCCUPANTS IN THIS SINGLE FAMILY RESIDENCE. NUMBER | | | OF PEOPLE DOESN'T MATCH NUMBER OF PEOPLE SPECIFIED ON | | | THE ENERGY CALCULATIONS. ALSO, CLARIFY WHY THE | | | CALCULATIONS ARE CONSIDERING 2 PEOPLE IN THE DINING | | | AREA?. THE NUMBER OF PEOPLE MAY AFFECT THE SIZING OF | | | THE EQUIPMENT. SEC. R403.6.1 FBC-ENERGY CONSERVATION | | | DOESN'T ALLOW ANY FACTORS THAT WILL AFFECT THE SIZING | | | OF THE EQUIPMENT. REVISE AS REQUIRED. (REPEAT COMMENT). | | | | | | 2- THE TRANSFER DUCT SIZE SPECIFIED ON THE A/C PLAN FOR | | | THE MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED | | | RETURN AIR. SEC. M1602.4. ALL THE SUPPLY AIR INTO THE | | | MASTER BEDROOM NEEDS TO BE CONSIDERED, INCLUDING THE | | | BATHROOM AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4 | | | FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS | | | REQUIRED. (REPEAT COMMENT). | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|