| Notes |
| Date |
Text |
| 2017-01-09 15:25:52 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW | | | CHECKLIST. . | | | CODE: FBC, 5TH EDITION (2014). | | | | | | | | | 1- BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". | | | ENGINEER OF RECORD TO REVISE EXPOSURE OR PROVIDE | | | ENGINEERING ANALYSIS FOR AN "INTERMEDIATE EXPOSURE" AS | | | REQUIRED BY THE EXCEPTION ON SEC. R301.2.1.4 | | | FBC-RESIDENTIAL. NOTE: REVISE DOORS/WINDOWS DESIGN | | | PRESSURES ACCORDINGLY. (REPEAT COMMENT). | | | | | | 2- SHEET A-2: WINDOWS SPECIFIED FOR BEDROOM LOCATED | | | ADJACENT TO THE GARAGE DON'T FIT ON THE OPENING SIZE | | | SPECIFIED ON PLANS. THE WIDTH DIMENSION WAS CHANGED | | | FROM 5'-2" TO 62". THIS IS THE SAME DIMENSION. THE | | | SPECIFIED WINDOWS AND MULLION DON'T FIT IN THIS | | | OPENING. REVISE OPENING WIDTH AS REQUIRED. SEC. 107.2.1 | | | CITY AMENDMENTS. (REPEAT COMMENT). | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|