| 2016-12-12 11:47:56 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | 1- THE PERSON WHO PREPARED THE LOAD CALCULATIONS IS THE |
| | SAME PERSON WHO PREPARED THE ENERGY CALCULATIONS. SEE |
| | BUILDING REVIEW COMMENTS FOR REQUIRED ENERGY |
| | CALCULATIONS REVISIONS AND REVISE THE LOAD CALCULATIONS |
| | AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- THE LOAD CALCULATIONS ARE CONSIDERING 12 PEOPLE AS |
| | THE OCCUPANTS IN THIS SINGLE FAMILY RESIDENCE. THE |
| | NUMBER OF PEOPLE LOOKS A LITTLE BIG HIGH FOR A THREE |
| | BEDROOM SINGLE FAMILY RESIDENCE. THE HIGH NUMBER OF |
| | PEOPLE MAY AFFECT THE SIZING OF THE EQUIPMENT. SEC. |
| | R403.6.1 DOESN'T ALLOW ANY FACTORS THAT WILL AFFECT THE |
| | SIZING OF THE EQUIPMENT. REVISE AS REQUIRED OR PROVIDE |
| | DOCUMENTATION SHOWING WHY A HIGHER NUMBER OF PEOPLE |
| | NEED TO BE CONSIDERED. |
| | |
| | 3- LOAD CALCULATIONS TO INCLUDE THE EQUIPMENT |
| | MANUFACTURER'S AND MODEL NUMBER ALONG WITH THE SENSIBLE |
| | AND TOTAL COOLING CAPACITIES AS REQUIRED BY SEC. |
| | R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | NOTE: COORDINATE WITH A/C PLAN SUBMITTED. |
| | |
| | 4- THE TRANSFER DUCT SIZE SPECIFIED ON THE A/C PLAN FOR |
| | THE MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED |
| | RETURN AIR. SEC. M1602.4. ALL THE SUPPLY AIR INTO THE |
| | MASTER BEDROOM NEEDS TO BE CONSIDERED, INCLUDING THE |
| | BATHROOM AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS |
| | REQUIRED. |
| | |
| | 5- CONDENSER UNIT TIE-DOWN CLIP PRODUCT APPROVAL |
| | SUBMITTED: PROVIDE CURRENT (2014 CODE) AND LEGIBLE |
| | PRODUCT APPROVAL. |
| | FAC 61G20-3.002(33). |
| | |
| | |