| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| | |
| | 1] PROVIDE A RISER DIAGRAM WITH SERVICE FEEDER WIRE |
| | SIZE, CONDUIT DETAIL INCLUDING RACEWAY TYPE & SIZE, |
| | GROUNDING DETAIL WITH ELECTRODE CONDUCTOR SIZE. FBC- |
| | 107.3.5.3 |
| | |
| | 2] SHOW A GFCI OUTDOOR RECEPTACLE OUTLET FOR THE W/H |
| | IGNITION. |
| | |
| | 3] GARAGE DOOR MOTOR RECEPTACLE OUTLET REQUIRES GFCI |
| | PROTECTION PER FBC-R SEC E3902.2. |
| | |
| | 4] CARBON MONOXIDE ALARM REQUIRED WITHIN 10' OF |
| | SLEEPING ROOMS DUE TO THE ATTACHED GARAGE PER FBC-R SEC |
| | 315.1 |
| | |
| | 5] CLARIFY SMOKE ALARM LOCATED IN THE KITCHEN TO BE |
| | LISTED FOR THE USE FOR INSTALLATION NEAR COOKING |
| | APPLIANCES & EQUIPPED WITH A SILENCING MEANS FEATURE IN |
| | ACCORDANCE WITH NFPA 29.8.3.4 . |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |